Single Burning Item (SBI) The Single Burning Item (SBI) test EN 13823 is one of the tests in the Euroclass system.

It is the main reaction to fire test for building products and investigates the response of a product in a corner configuration when it is exposed to a thermal attack typifying fire involving a single burning item.

It was the FIRE design of the SBI equipment that formed the cornerstone for the extensive European Commission sponsored 'round-robin' exercise that was carried out to validate this test method. It is relevant to classification of the product into classes A2, B, C or D as set out in Commission Decision of 8th February 2000 - implementing Council Directive 89/106/EEC. EN 13823 excludes flooring materials.


Features

·
System comprises movable specimen holder, frame, hood, collector and measuring tube assembly
 
·
Left and right oriented specimen holders available
·
Flow measurement utilising bi-directional probe and differential pressure transducer
·
Temperature measurement at different locations inside the measuring tube
·
Smoke measurement system according to DIN 50055
·
Gas sampling probe
·
19" rack housing PLC system and mass flow controllers PLC control system for main and auxiliary burners with fully automated test and calibration sequencing
·
Gas flow measured by high accuracy Mass Flow Controller with a range of 0-105kW at 70nl/min, accurate to 0.8% at 30kW Burners are fitted with flash-back protection and electronic flame sensors with safety cut-off system for enhanced safety Data Acquisition system Complete operating instructions
 
·
CE-marked


What is measured

·
Time, in s
·
Mass flow of propane through the burner, in mg.s-1
·
Pressure difference in the general measuring section, in Pa
·
Relative light intensity, dimensionless
·
O2 concentration in VO2 /Vair (%)
·
CO2 concentration in VCO2 /Vair (%)
·
Ambient temperature at air inlet at bottom of trolley, in K
·
Three temperatures in general measurement section, in K
·
Four temperatures just after the hood to measure the temperature rise, in K