生产商:FIRE
Instrumentation & Research Equipment
Limited,UK
|
|
Single
Burning Item (SBI) The Single Burning Item
(SBI) test EN 13823 is one of the tests in
the Euroclass system.
It is the main reaction
to fire test for building products and investigates
the response of a product in a corner configuration
when it is exposed to a thermal attack typifying
fire involving a single burning item.
It was the FIRE design of the SBI equipment
that formed the cornerstone for the extensive
European Commission sponsored 'round-robin'
exercise that was carried out to validate
this test method. It is relevant to classification
of the product into classes A2, B, C or D
as set out in Commission Decision of 8th February
2000 - implementing Council Directive 89/106/EEC.
EN 13823 excludes flooring materials.
|
·
|
System
comprises movable specimen holder, frame,
hood, collector and measuring tube assembly
|
|
·
|
Left and right
oriented specimen holders available |
·
|
Flow measurement
utilising bi-directional probe and differential
pressure transducer |
·
|
Temperature measurement
at different locations inside the measuring
tube |
·
|
Smoke measurement
system according to DIN 50055 |
·
|
Gas sampling
probe |
·
|
19"
rack housing PLC system and mass flow controllers
PLC control system for main and auxiliary
burners with fully automated test and calibration
sequencing |
|
·
|
Gas
flow measured by high accuracy Mass Flow
Controller with a range of 0-105kW at 70nl/min,
accurate to 0.8% at 30kW Burners are fitted
with flash-back protection and electronic
flame sensors with safety cut-off system
for enhanced safety Data Acquisition system
Complete operating instructions |
|
|
|
·
|
CE-marked |
·
|
Time,
in s |
·
|
Mass
flow of propane through the burner, in mg.s-1
|
·
|
Pressure
difference in the general measuring section,
in Pa |
·
|
Relative
light intensity, dimensionless |
·
|
O2
concentration in VO2 /Vair (%) |
·
|
CO2
concentration in VCO2 /Vair (%) |
·
|
Ambient
temperature at air inlet at bottom of trolley,
in K |
·
|
Three
temperatures in general measurement section,
in K |
·
|
Four
temperatures just after the hood to measure
the temperature rise, in K |
|
|
|
Copyright
©2002~2003 Rakon Science & Technology
Ltd
|
|
|